ENERGY

WARNING SYSTEM

About

Developed with national resources, the Warning System is a reliable and high-performance product that has reached the highest technology readiness level (THS 9) and complies with international standards. This system, which plays a critical role for the safety and efficiency of Turkey's power generation infrastructure, offers a flexible solution thanks to its ability to be designed specifically for the needs of power plants, and reduces foreign dependency in this field.

warning system img7

Product Overview

It is a vital system for the stable operation of synchronous generators in power generation plants. It precisely controls the output voltage and reactive power of the generator by providing the required direct current (DC) to the field windings in the rotor of the generator. In this way, it increases the stability of the overall power system and includes generator protective functions.

Product Name

Warning System

Product Type

Final Product

Developer Research Groups

Energy Technologies BY - Power Electronics AG

Production and Technology Status

Production Capacity

1 in 12 months (Project based).

Current Status

It can be actively produced.

Technology Readiness Level (THS)

THS 9

Owned Standards

Fully compliant with IEC 60076 series (1 to 5) and the Electricity Market Grid Regulation.

Technical Capabilities and Capacity

The National Warning System is specially designed according to the characteristics of the power plant and generator where it will be installed, and is focused on high reliability and performance.

Design Flexibility

Customized design and production according to the requirements of the system.

High Reliability

Uninterrupted operation even in case of failure thanks to redundant rectifiers, control units and power supplies.

Advanced Data Recording

20 millisecond sampling rate and the capacity to record data and store it for 3 months.

Operational Capabilities

It has modern functions such as "inverter operation", which can pump energy from the field windings back into the grid during generator shutdown.

Protection Functions

The system has built-in limiters and protection mechanisms that protect the generator and the warning system.

System Types and Capacities

Static Warning System (for Brushless and Brushed Generators)
Maximum Output Voltage: 600V DC
Maximum Output Current: 2000A DC

Dynamic Warning System (for Rotary Diode Brushless Generators)
Maximum Output Voltage: 100V DC
Maximum Output Current: 50A DC